Alarm
Display Unit LLD 10/15 |
OPERATION
On the panel, the sensors indicator flashes when
the pre-set time delay has elapsed. At the same time the output
group(s) attached to the alarm point are activated. Further error
messages are not blocked by earlier signals. Error messages are
acknowledged by pressing the "RESET" button. The output
terminal are then reset, at the same time as the alarm indicator
changes to a constant light. When the fault has been fixed and the
sensors switch has return to its normal state, then the alarm indicator
goes out. If a fault should fix itself and the switch reset itself
before acknowledgement has occurred, then the panel recalls the
fault. The flashing light and output contact are activated until
acknowledgement has occurred. The LLD 10 unit is thus equipped with
a memory function and is always ready for a new alarm.
Pressing the TEST button makes a standard test of operation. This
simulates a fault across the alarm terminals of the system.
The green operation indication's diode lights up when voltage is
following through the panel..
SECURITY
The LLD 10 unit is constructed for surveillance work even under
extreme conditions. Like all IMSAB alarm products it is equipped
with multiple protection against accidental connection to voltages,
interference etc. Alternating voltage can be fed directly into the
panel without the requirement for stabilisation. It also has a built
in zero voltage control, which means that the output relay for each
alarm group is normally junctured. In case of alarm or voltage falloff
the output relays break.
CE-tested and approved according to: EN50082-2; IEC801-2:1991; ENV50140;
ENV50141; IEC801-4.
INSTALLATION
The LLD 10 unit is designed for mounting on a
DIN-rail in a normal enclosure and its compact form make it easy
to fit in any enclose. There is a master and slave version. If more
than 10 alarm points are required in the construction, then it can
be complemented with slaves with 15 points. Connection is made to
the unit by an easily accessible screw terminal block,which can
be fitted with a corresponding terminal strip. This connection method
means that no cable need to be loosened after installation. In a
few moments it is easy to part the cable from the panel.
PROGRAMMING
The LLD10M unit can be adjusted in a number of
ways. Here are a number of the key features of the LLD10M unit:
- Alarm inputs work with normally open
(NO) or normally closed (NC) contacts. Individually selectable
for each input.
- For each alarm input a separate time delay
of 75 seconds can be selected.
- Each alarm input can be connected to none
or several relay outputs. The LLD10M unit is delivered with a
standard setting of alarm inputs and relay outputs.
Standard setting:
- All alarm inputs are set to work with
normally open (NO) alarm contacts.
- All alarm inputs are set at 0 seconds time
delay.
- All alarm inputs are connected to the A-alarm
relay output.
PROGRAMMING CONSTRUCTION
Construction of the programming method is such
that:
1- Firstly is selected which unit in the system where alarm inputs
exist that is to be programmed or changed. (The number of units
depends on how large the system is, namely between one to seven
units).
2- Once the unit is selected, next is selected which of the five
(5) rows of inputs the input(s) are to be found.
3- Once the actual row is selected, then the individual alarm input
that is to be programmed or changed is selected. (Here there are
five (5) to select from).
4- At the individual input level there are three (3) different setting
to select:
- Firstly is selected if the input should work
as a normally closed (NC) or normally open (NO) alarm contact.
- Next is selected, by adding time intervals,
which time delay the input should have from the physical alarm
until the LLD10M system informs the alarm categories that the
alarm has occurred.
- Finally is selected which alarm categories
(A-B-C alarms) that should be activated with an alarm at that
alarm input. Between 0-3 can be selected.
SPECIFICATIONS
Power Supply: |
24V AC/DC ± 20%; 80-200mA |
Outputs: |
One change-over contact per alarm group (A-B-C alarm)
max 24VDC 1A/ 48VAC 1A res. last |
Time delay: |
Individually selectable delay 0.05-75 sec/channel |
Front: |
Grey plastic with pockets for the alarm points |
Dimensions: |
75x150x60 mm (hxbxd) |
Ambient Temperature: |
+5°C to +40°C |
Humidity: |
10- 90% Relative Humidity, not condensed |
Legends: |
Space for 2-3 5-point legends |
Indicator: |
Red light diodes = error signals |
Enclosure class: |
P20 |
ORDERING INSTRUCTIONS
Master LLD10M
Slave LLD15S
Option: Interface board for communication with a controlling supervising
computer (RS232). |