LB 10 Master/Slave Panel


OPERATION

A fault signal activates the timer on the card.

After the individually pre-set time has elapsed the indicator lamp starts to flash, while at the same time the output relay for the group involved is activated.

The signal is acknowledged by pressing the common red accept button, which resets the output contacts and changes the lamp to a steady light.

Finally, when the sensor contacts return to their normal state, the indicator lamp goes out.

LB-10 can be supplied in a version without indicator lamps, for use in a mimic diagram or similar types of display.

SECURITY

LB-10 is designed for severe mechanical and electrical environmental conditions. It is provided with protection against polarity reversal and accidental connection of voltage.

The unit is designed to indicate voltage failures; each group relay is normally activated. In the alarm state the relay is deactivated and a signal can be given with, for example, a horn. The same thing happens when the supply voltage is interrupted.

Normal function testing is carried out by pressing the black button, which simulates a fault on each alarm channel. In addition, the unique group alarm test gives a more sophisticated safety-assurance test. It checks that each individual alarm point contributes to its group output.

LB-10 is fitted with a running light indicator, to confirm that the power is connected. Lamps are checked manually by pressing the black function test button and the red accept button, simultaneously. The cards fit into strong guide rails and can be locked into position. The unit is in accordance with CE-standards: EN 50 082-2; IEC 801-2:1991; ENV 50 140; ENV 50 141; IEC 801-4.

INSTALLATION

LLB-10 is designed for panel mounting.

The unit is available in both master and slave versions and the system can, therefore, be built up in stages with, or from the start comprise, one master and up to 9 slave units.

The test and accept facilities are provided only on the master unit, which carries out these function on behalf of the slave units.

The unit is connected through plug-in terminal cards. One of these is for the external leads and the other for internal connections between the master and slave units. This makes connection very simple, whilst allowing for easy separation of the complete unit.

SPECIFICATIONS

Supply voltage: 24V or 48V DC ± 20% smoothed or unsmoothed
Supply current: Normal condition 0.2A, Alarm condition (max.) 0.7A
Time delay: 0.5 - 20 sec. adjustable for each alarm card
Number of alarm groups: 2 or 4 per system (A-B-C-D alarm)
HyDELETREe: max 80% not condensed
Output contacts: One change-over contact per alarm group. Contact rating 100V, 100VA, resistive load
Front: Dull black aluminium
Main dimensions: DIN 144x144x35 mm
Panel recess: 125x125 mm
Legends: Space for legends 50x15 mm, or engraved on lamp screens
Indicators: Red lamps = faulty indication (Ba9s 24V 50mA or 48V 40mA)
Main dimensions: 350x96x155 mm, panel mounting.
330x150x75 mm, terminal mounting
Panel recess: 330x76 mm (for service handling, we recommend 20 mm between each panel)
Max permissible external cable resistance: 1000 ohm
 
 