LDC
10 Master/Slave Panel |
OPERATION
LDC-10 can be fed from an AC supply.
The unit has flashing indicator lights and a memory. Alarms can
be graded into three groups according to urgency. The channel memory
and the actual output contact has expired. The alarm signal is acknowledged
with the red reset button and the corresponding lamp changes from
a flashing to a steady light, while at the same time the output
contact for the alarm group is reset.
The unit is also fitted with special plug-in connector (s), which
supply extra information, such as alarm point status, to external
units, for example, through an interface board (731) to a computer.
SECURITY
LDC-10 is designed for severe mechanical and electrical environmental
conditions.
It is provided with protection against polarity reversal and accidental
connection of voltage.
The unit is designed to indicate voltage failures; each group relay
is normally activated. In the alarm state the relay is deactivated
and a signal can be given with, for example, a horn. The same thing
happens when the supply voltage is interrupted.
All alarm channels are checked by the function test, including channels
in alarm condition. When the black function test button is pressed,
faults are simulated on all channels and all timers are started.
Simulation of the correction of existing alarms occurs during the
time the button is held pressed in. The button is released after
30 seconds, when all the timers have run out. The existing alarms
are then activated and the corresponding timers start. After a further
30 seconds, all alarm channels have, therefore, been tested.
None are left unchecked - a facility that is unique in alarm systems
of this size.
LDC-10 is fitted with a running light indicator to confirm that
the power is connected. Lamps are checked manually by pressing the
black function test button and the red accept button, simultaneously.
At the same time as the function test takes place, a group alarm
test is automatically made. This checks that all alarm channels
are contributing to their group alarm output.
The unit is in accordance with CE-standards: EN 50 082-2; IEC 801-2:1991;
ENV 50 140; ENV 50 141; IEC 801-4.
INSTALLATION
LDC-10 LD is designed for panel, cabinet or wall
mounting.
It is made only in the master version.
Systems with more than 10 alarm channels require additional panels.
Connection is made to the unit by an easily accessible screw terminal
block, which can be fitted with a corresponding terminal strip.
The use of this system means that cable connections need not be
disturbed once the installation is complete, and that the unit can
be disconnected very quickly.
SPECIFICATIONS
Supply voltage: |
24V AC/DC ± 20% |
Supply current: |
Normal condition 0.1A, Alarm condition 0.4A |
Time delay: |
Individually adjustable time 0,5-20 sec. each channel |
Output contacts: |
One change-over contact per alarm group (A, B and C alarms).
Selection device on each alarm point contact rated max 100V
4A resistance load. |
Front: |
Dull black aluminium |
Main dimensions: |
DIN 350x96x160 mm |
Panel recess: |
330x76 mm (19" 64x455mm) |
Ordering Instructions: |
12044 LDC 10 Master / 12045
LDC 10 Slave |
Extra accessories
(731): |
Relay
circuit board for an interface to a computer or remote alarm |
|
|