Alarm Display Unit LH 10 110DC


OPERATION

The alarms can be graded into two groups, according to the degree of urgency.

Each group is provided with a group alarm output and adjustable time-delay.

The sensor contacts close (or open) and the corresponding lamp flashes. The memory and the output contacts are activated when the pre-set time for the group has expired.

The alarm signal is acknowledged by pressing the red accept button; the flashing lamp becomes steady and the group output contacts return to their normal state. When the fault has been corrected and the sensor has returned to its normal state, then the indicator lamp goes out.

Legends can be fitted to the indicator lamps or the screens can be engraved. With LH-10 it is possible to connect a remote accept facility and the unit can, also, be equipped for use in unmanned power installations.

INSTALLATION

LH-10 is designed for panel mounting into a power cabinet. LH-10, for use in power installations, is made only in the master version.

The unit is connected through an easily accessible screw terminal block, each fitted with an additional terminal strip (plug and socket). Connection is simple and the terminal arrangement allows the unit to be separated quickly, without disturbing the cable connections.

A selector switch, which can be easily changed on the circuit board of the unit, is used to connect the alarm points to the desired group alarm output (A or B alarms). In the case of normally closed sensor contacts, a wire link in the actual channel circuitry has to be cut off.

SECURITY


LH-10 is designed for severe mechanical and electrical environmental conditions.

It is provided with protection against polarity reversal and accidental connection of voltage.

The unit is designed to indicate voltage failures; each group relay is normally activated. In the alarm state the relay is deactivated and a signal can be given with, for example, a horn. The same thing happens when the supply voltage is interrupted.

Testing for normal function is carried out by pressing the black test button, which simulates faults on the alarm channels of the system. The unit is in accordance with CE-standards: EN 50 082-2; IEC 801-2:1991; ENV 50 140; ENV 50 141; IEC 801-4.

SPECIFICATIONS

Supply voltage: 110V DC ± 20%
Supply current: Normal condition 0.02A, Alarm condition 0.25A
Time delay: 0,5 - 20 sec. adjustable common line for each alarm group
Number of alarm groups: Max 2 per panel (A and B alarms). Selection device on each alarm channel.
Output contacts: Each alarm group has 1 set of closing contacts. Contact rating 100V, 100VA, resistive load.
Front: Natural colour anodised aluminium
Legends: Film legend 24x32 mm or engraved on lamp screen
Lamps: Ba9s 130V 20mA
Main dimensions: 88x482x140 mm
Panel recess: 64x445 mm
Max permissible external cable resistance: 500 ohm
Ordering Instructions: 12032 LH 10
Extra accessories: 1022 Relay circuit board for an interface to computer or 10 remote alarms

 
 


© 2002 IMSAB • Tel: +46 31 29 06 40 • Fax: +46 31 29 48 29
info@imsab.se • Guldringen 1, SE-426 52, V.Frölunda, Sweden