Alarm
Display Unit LLC 10 |
OPERATION
A sensors flashes when the pre-set time delay
has elapsed. At the same time, the output group to which it is connected
is activated. The signal is acknowledged by pressing the red RESET
button. This releases the output contact and the flashing light
becomes steady.
When the fault has been corrected and the sensor
contact has returned to its normal state, the indicator lamp goes
out. If the fault self-corrects and the sensor contact returns before
acknowledgement, then the fault remains in the units memory, the
light flashes and the output contact remains activated, until the
accept button is pressed.
LLC-10 is equipped with a channel memory. The
unit is always ready to receive new alarm signals, independent of
system status. The panel can be provided with legends for each alarm
channel or with a common 10 point legend.
SECURITY
LLC-10 is designed for severe mechanical and electrical environmental
conditions.
It is provided with protection against polarity
reversal, accidental connection of voltage, interruptions etc. The
unit is designed to indicate voltage failures: each group relay
is normally activated. In the alarm state the relay is deactivated
and a signal can be given with, for example, a horn. The same thing
happens when the supply voltage is interrupted.
Its limited size and depth allows it to be easily
mounted in panels, walls and similar spaces. Normal function testing
is carried out by pressing the test button, which simulates faults
on the alarm channels in the system.
The unit is in accordance with CE-standards: EN 50 082-2; IEC 801-2:1991;
ENV 50 140; ENV 50 141; IEC 801-4.
INSTALLATION
LLC-10 is designed for panel, cabinet or wall
mounting.
It is made only in the master version.
Systems with more than 10 alarm channels require
additional panels.
Connection is made to the unit by an easily accessible
screw terminal block, which can be fitted with a corresponding terminal
strip. The use of this system means that cable connections need
not be disturbed once the installation is complete, and that the
unit can be disconnected very quickly.
SPECIFICATIONS
Supply voltage: |
24V AC/DC ± 20%; 0,1-0,2A |
Supply current: |
Normal condition 0.1A, Alarm condition 0.2A |
Time delay: |
Individually adjustable time 0,5-20 sec. each channel |
Ambient temperature: |
min -10€C max 55€C |
Hygroscopic moisture: |
max 80% not condensed |
Output contacts: |
One change-over contact per alarm group (A and B alarms).
Selection device on each alarm point contact rated 24V 1A resistive
load. Max 30V RMS, or 60VDC (Selv or Telv) |
Front: |
Dull black aluminium with plastic cover IP44 and together
with gasket IP65 |
Main dimensions: |
DIN 144x144x35 mm |
Panel recess: |
125x125 mm |
Legends: |
Space for individual channel legends or common 5 channel legends |
Indicators: |
Red LED for unacknowledged alarm |
Ordering Instructions: |
12040 LLC 10 |
Extra accessories
(1084): |
Relay
circuit board for an interface to a computer or remote alarm |
|